Range of product | Easy Modicon M100 |
---|---|
Product or component type | Logic controller |
[Us] rated supply voltage | 100...240 V AC |
Discrete I/O number | 16 |
Discrete input number | I2...I5: 4 fast input I6...I8: 3 regular input I0...I1: 2 high speed input |
Discrete output number | 7 relay |
Discrete input voltage | 24 V |
Discrete input voltage type | DC |
Discrete input current | 7 mA for regular input 7 mA for fast input 9 mA for high speed input |
Discrete output voltage | 24 V DC 220 V AC |
Discrete output current | 2 A |
Discrete output type | Relay normally open |
Power consumption in VA | 3040 VA at 100...240 V AC (with max I/O) |
Supply voltage limits | 85264 V |
---|---|
Voltage state 1 guaranteed | >= 15 V for input |
Voltage state 0 guaranteed | <= 5 V for input |
Network frequency | 50/60 Hz |
Inrush current | 50 A |
Input impedance | 3.3 kOhm for regular input 3.3 kOhm for fast input 2.81 kOhm for high speed input |
Response time | 10 ms turn-on, Q0...Q6 terminal(s) for relay output 10 ms turn-off, Q0...Q6 terminal(s) for relay output 35 µs turn-on, I2...I5 terminal(s) for fast input 100 µs turn-off, I2...I5 terminal(s) for fast input 5 µs turn-on, I0...I1 terminal(s) for high speed input 5 µs turn-off, I0...I1 terminal(s) for high speed input 35 µs turn-on, I6...I8 terminal(s) for regular input 100 µs turn-off, I6...I8 terminal(s) for regular input |
Configurable filtering time | 0 ms for input 3 ms for input 12 ms for input |
Output voltage limits | 30 V DC 250 V AC |
Maximum current per output common | 4 A at COM 0 4 A at COM 1 |
Electrical durability | 100000 cycles AC-12, 240 V, 480 VA, resistive 100000 cycles DC-12, 24 V, 48 W, resistive |
Switching frequency | 0.1 Hz with maximum load 5 Hz without maximum load |
Mechanical durability | 20000000 cycles for relay output |
Minimum load | 10 mA at 5 V DC for relay output |
Memory capacity | 1024 kB internal flash with 10000 instructions for backup of programs |
Data storage equipment | 32 GB micro SD card (optional) |
Execution time for 1 KInstruction | 0.3 ms for event and periodic task |
Execution time per instruction | 0.2 µs Boolean |
Exct time for event task | 60 µs response time |
Regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
Control signal type | Quadrature (x1, x2, x4) at 60 kHz for fast input (HSC mode) Pulse/direction at 60 kHz for fast input (HSC mode) Single phase at 60 kHz for fast input (HSC mode) CW/CCW at 60 kHz for fast input (HSC mode) |
Counting input number | 2 fast input (HSC mode) at 60 kHz 32 bits |
Integrated connection type | USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with terminal block connector and RS485 interface Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface |
Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB |
Communication port protocol | USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network |
Local signalling | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (green) for SL1 1 LED per channel (green) for I/O state |
Electrical connection | removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 4 terminal(s) for connecting the serial link1 Mini B USB 2.0 connectorfor a programming terminal removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply |
Maximum cable distance between devices | Shielded cable: <10 m for fast input Shielded cable: <10 m for high speed input Unshielded cable: <150 m for output Unshielded cable: <50 m for regular input |
Insulation | Between input and internal logic at 560 V AC Between fast input and internal logic at 560 V AC Between input groups at 560 V AC Non-insulated between inputs Between output and internal logic at 1780 V AC Between output groups at 1780 V AC Between supply and internal logic at 1780 V AC |
Sensor power supply | 24 V DC |
Mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715 |
Height | 90 mm |
Depth | 70 mm |
Width | 110 mm |
Net weight | 0.31 kg |
IP degree of protection | IP20 with protective cover in place |
---|---|
product certifications | CE |
Standards | EN/IEC 61010-2-201 EN/IEC 61131-2 |
Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to EN/IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to EN/IEC 61000-4-3 Conducted emission - test level: 79 dBV/m QP/66 dBV/m AV (power lines (AC)) conforming to EN/IEC 55011 Conducted emission - test level: 73 dBV/m QP/60 dBV/m AV (power lines (AC)) conforming to EN/IEC 55011 Radiated emission - test level: 40 dBV/m QP class A (10 m) conforming to EN/IEC 55011 Radiated emission - test level: 47 dBV/m QP class A (10 m) conforming to EN/IEC 55011 Magnetic field at power frequency - test level: 30 A/m (I/O) conforming to EN/IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to EN/IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to EN/IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 0.5 kV class A (power lines (DC)) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV class A (power lines (AC)) conforming to EN/IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (relay output) conforming to EN/IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6 |
Shock resistance | 15 gn for 11 ms 30 gn for 6 ms |
Immunity to microbreaks | 10 ms |
Vibration resistance | 3.5 mm at 58.4 Hz on symmetrical rail 1 gn at 8.4150 Hz on symmetrical rail 3.5 mm at 58.4 Hz on panel mounting 3 gn at 8.4150 Hz on panel mounting |
Relative humidity | 1095 %, without condensation (in operation) 1095 %, without condensation (in storage) |
Ambient air temperature for operation | 055 C (horizontal installation) |
Ambient air temperature for storage | -2570 C |
Pollution degree | <= 2 |
Operating altitude | 0...2000 m |
Storage altitude | 03000 m |